Riku Mattila :verified: on Nostr: npub1w2usc…tnua0 In principle, they are feeding the circuit after the fuse. For ...

npub1w2uscas6hj9mrls7fxdgssstm3q03ytxrack83q2y2q3gdsnz3ksvtnua0 (npub1w2u…nua0) In principle, they are feeding the circuit after the fuse. For example, a 1.5 mm˛ cable inside an insulated wall can be loaded at max 13.5 A to keep it <70 °C. A 10 A fuse is barely able to ensure that but not if you feed, say, 5 A after the fuse.